Modus HVAC Differential Pressure Transmitters
T Series
Modus T Series of Differential Pressure Transmitters measure low pressures and feature low power consumption with a variety of analog signal outputs. A wide selection of standard pressure ranges and electrical ratings is available.
Modus T Series Transmitters are an excellent choice for many HVAC, process and automation monitoring requirements. These transmitters monitor: filter differential pressures, fan static pressures, clean room pressures, variable air volume systems and velocity pressures. They have been used for bubbler level systems, leak detection and in medical and analytical instruments.
- Monitoring Filter Differential Pressure
- Fan Static Pressures
- Clean Room Pressurization
- Variable Air Volume Systems
- Bubbler Level Systems
- Measures differential, gage pressure, or vacuum
- Suitable for air or inert gases
- No moving parts to wear out
- Proven long term stability of piezoresistive devices
- Only 316 stainless steel in contact with the fluid
- All welded construction
Performance | |
Accuracy | ± 1% of span (including non-linearity and hysteresis) |
Effect of Static Pressure on Differential Pressure Measurement | Less than ±0.25% for static pressure change from 0 to 100% or ±0.5% for 6 psid (50 kPa) range |
Operating Temperature Range | 32°F to 115°F (0°C to 45°C) |
Storage Temperature | -20°F to 160°F (-30°C to 70°C) |
Operating Humidity Range | 10% to 90% RH, non-condensing |
Shock Resistance | 10 G (11 ms) |
Vibration Resistance | 5 G 3 to 50 Hz |