- Wall mount sensors are used to control a specific indoor area such as a conference room, classroom, meeting hall, etc.
- Indoor growing
Telaire T8000-R Series
Wall Mount CO2 & Temperature Transmitter
Telaire T8000-R Series of Wall Mount CO2 and Temperature Transmitters consists of low cost, high performance CO2 and temperature transmitters with relay for building controls and indoor growers markets. It works seamlessly with building automation systems, and allows you to simply and effectively control fresh air into a ventilated space to meet regulated standards, providing immediate energy savings. Relay control can be used to control fresh air when no building automation system is available. The Telaire 8000-R series can also be used with its built-in relay to control CO2 producing equipment to assist with plant growth.
- Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low cost package
- Patented ABC Logic™ self-calibration system eliminates the need for manual calibration in most applications
- Lifetime CO2 calibration guarantee when using ABC Logic™
- Mounting plate with two-piece terminal blocks provide quick, easy wiring
- Gas permeable, water resistant CO2 diffusion filter prevents particulate and water contamination of the sensor
- Locking screw secures cover and sensor to the mounting bracket for tamper resistance
- Sensors are shipped factory calibrated
- Modern enclosure
- Conformal coating on 0-5000 ppm models
- Low cost
- Reliable (20 years of low-cost infrared sensor manufacturing)
- Available CO2 and Temperature output options: Voltage 0-10V or 0-5V (switch selectable) Or current 4-20 mA, Relay
- UIP software compatible for customizations
- CE, RoHS, REACH and WEEE compliant
- Lifetime calibration warranty
- Relay output
Sensing Method | Non Dispersive Infrared (NDIR), gold plated optics, diffusion or flow through sampling (with Telaire’s Patented ABC Logic Self Calibrated Algorithm) |
Measurement Range | 0 to 5000 ppm** |
Dimensions | Overall 60 mm X 35 mm X 15 mm approx |
Accuracy | 400-5000 ppm ± 75 ppm or 10% of reading, whichever is greater* |
Temperature Dependence | 0.2% FS per °C |
Stability | < 2% of FS over life of sensor (15 years typical) |
Pressure Dependence | 0.13% of reading per mm Hg |
Calibration Interval | Not required |
Response Time | 7 minutes (approx) |
Signal Update | Every 4 seconds |
Warm Up Time |
|
Operating Conditions |
|
Storage Conditions | -40°F to 158°F (-40°C to 70°C) |
Output | I2C Digital, see T6700 Series Application Guide for detail |
Protection | IP65 |
Power Supply Requirements |
|
Warranty Terms | 12 months |
Compliance |
|
* Tolerance based on span gas of ±2% |
English
English
Demand Control Ventilation Q&A - Telaire Application Note
Common CO2 Wiring Issues - Telaire Application Note
CO2-based Ventilation Control | Where Required and Recommended - Telaire Application Note
CO2 Sensor Sniffs Out Human Smugglers - Telaire Application Note
Carbon Dioxide (CO2) and Combustion Sensing - Telaire Application Note
ABCLogic™ Self Calibration Feature - Telaire Application Note
English
T8100-D-R
T8200-D-5P-R
T8300-B-R
T8300-DB-R