- Demand-controlled ventilation in a specific indoor area, such as a conference room, classroom, meeting hall, etc.
Telaire T5100 Series
Wall Mount CO2 TransmitterS
Telaire T5100 Series of Wall Mount CO2 Transmitters offers low cost, high performance CO2 transmitters for the building controls market. It works seamlessly with building automation systems, and allows you to simply and effectively control fresh air. Demand-controlled ventilation using CO2 sensors prevents energy loss from over-ventilation while maintaining indoor air quality.
- Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low cost package
- Patented ABC Logic™ self-calibration system eliminates the need for manual calibration in most applications
- Lifetime CO2 calibration guarantee when using ABC Logic™
- Mounting plate with two-piece terminal blocks provide quick, easy wiring
- Gas permeable, water resistant CO2 diffusion filter prevents particulate and water contamination of the sensor
- Locking screw secures cover and sensor to the mounting bracket for tamper resistance
- Sensors are shipped factory calibrated
- Modern enclosure
- Low cost
- Reliable (20 years of low-cost infrared sensor manufacturing)
- UIP software compatible for customizations
- CE, RoHS, REACH and WEEE compliant
- Lifetime calibration warranty
- Two enclosure sizes for regional acceptance
Sensing Method | Non-dispersive infrared (NDIR) absorption Gold-plated optics Patented ABC Logic self calibration algorithm |
---|---|
CO2 Measurement Range | 0 to 2000 ppm (0 ppm = 0 V, 4 mA) |
CO2 Accuracy | ±30 ppm or 3% of the reading shown, whichever is higher * |
Power Supply Requirements | 18-30 VAC RMS, 50/60 Hz, or 18 to 42 VDC,polarity protected*AHRAE — regulation 62 states maximum indoor CO2 level of 1000 ppm |
Power Consumption | Typical 0.7 W at nominal voltage of 24V AC RMS |
Temperature Dependence | 0.2% FS per °C (±0.11% per °F) |
Stability | <2% of FS over life of sensor (15 years) |
Pressure Dependence | 0.135% of reading per mm Hg |
Certifications | CE EMC, RoHS, REACH and WEEE compliant |
Signal Update | Every 5 seconds |
CO2 Warm-Up Time | <2 minutes (operational) 10 minutes (maximum accuracy) |
Operating Conditions | 32°F to 122°F (0°C to 50°C) 0 to 95% RH, non-condensing |
Storage Conditions | -40°F to 158°F (-40°C to 70°C) |
Flammability Classification | UL94 5VA |
Output | Field selectable voltage or current Field selectable voltage or current Voltage only (0-10 or 0-5V)- Current only (4-20 mA) |
Analog (CO2) | 0 to 5 V, or 0 to 10 V jumper selectable (100 Ω output impedance) Or 4 to 20 mA (RL maximum 500 Ω) Voltage and current outputs are not available simultaneously Digital to analog error ±1% |
English
Demand Control Ventilation Q&A - Telaire Application Note
Common CO2 Wiring Issues - Telaire Application Note
CO2-based Ventilation Control | Where Required and Recommended - Telaire Application Note
CO2 Sensor Sniffs Out Human Smugglers - Telaire Application Note
Carbon Dioxide (CO2) and Combustion Sensing - Telaire Application Note
ABCLogic™ Self Calibration Feature - Telaire Application Note
English